Volume 95, Issue 3 pp. 405-415
Research Article
Open Access

Simulation of Compression Heat Pump Cycles Using NH3/H2O Mixtures to Estimate Their Working Domains

Maximilian Loth

Corresponding Author

Maximilian Loth

Leibniz University Hannover, Institute of Thermodynamics, Welfengarten 1, 30167 Hannover, Germany

Correspondence: Maximilian Loth ([email protected]), Leibniz University Hannover, Institute of Thermodynamics, Welfengarten 1, 30167 Hannover, Germany.Search for more papers by this author
Prof. Dr.-Ing. Stephan Kabelac

Prof. Dr.-Ing. Stephan Kabelac

Leibniz University Hannover, Institute of Thermodynamics, Welfengarten 1, 30167 Hannover, Germany

Search for more papers by this author
First published: 22 November 2022

Abstract

A computer-aided process design methodology is used to determine the limits of NH3/H2O mixtures in different heat pump cycles from 20 °C to 150 °C. The evaluation is based on a defined parameter set consisting of the coefficient of performance, total heat transfer area and volumetric heat capacity. Simple cycles with two heat flows were chosen to meet good process integration capabilities. The results are shown in a sink outlet/temperature lift matrix considering current technical limits. R1366mzz(Z) in a standard compression cycle with internal heat exchanger serves as a benchmark. To provide temperatures up to 150 °C the lift of the heat pump has to increase to about 80 K of which only the wet compressions cycle with NH3/H2O is capable of. The working domains of NH3/H2O and R1366mzz(Z) are similar, when a two-stage compression for NH3/H2O is applied.

1 Introduction

The need to decrease the use of fossil fuels and the related CO2 emissions in the near future due to global warming is scientific consensus 1, but the resources to pursue the route by then are not. One scenario that is hoped to make a major contribution in future is the decarbonization of thermal energy with the help of heat pumps powered by renewable electricity 2. While heat pump sales in the domestic sector will continue growing in Europe 3 by available technology for temperatures below 70 °C, the potential in the industrial sector is widely untapped because of technological and economical constrains arising at temperatures above 70 °C 4. The curve of the total process heat flow in Fig. 1 indicates that temperatures greater than 100 °C are needed to open up considerable amounts of process heat. The presented data is limited to four industrial sectors with the most promising process integration capabilities of heat pumps, resulting in potentials for the chemical sector with sink flow temperatures up to 150 °C of 252 PJ a−1 (○) and for all four sectors of 547 PJ a−1 (*) 5. This is about 2 % respectively 5 % of the final energy consumption for heat of EU28's industry 6 or 0.4 % respectively 0.9 % of EU28's final energy consumption 7. Besides the absolute temperature levels of waste and process heat also an averaged minimal temperature lift between waste and process heat over all processes may be iteratively calculated according to
urn:x-wiley:0009286X:media:cite202200111-math-0001(1)

The evaluation of this equation for the chemical and total case are calculated by supposing a typical Carnot efficiency of ζ = 45 % 4 for real heat pumps and the two curves are also part of Fig. 1. At 150 °C the minimal averaged temperature lift required by the heat pump is between 77 K and 90 K. urn:x-wiley:0009286X:media:cite202200111-math-0002 of the chemical sector is higher than that for all sectors. The greyed area at temperatures above 150 °C in Fig. 1 is out of the scope of this study, due to current technical and economic limitations 4, 5.

Details are in the caption following the image
Total and chemical sector waste and process heat in EU28 5 by temperature level and related averaged minimal temperature lift. At 150 °C the heat pump potentials for the chemical sector and all four sectors are indicated by a circle respectively a star.
In addition to the demand and temperature levels, the study carried out by Marina et al. 5 showed that 70 % of the heat pump units have to be small sized with heating capacities below 5 MW. This requires some kind of standardized layout and serial production to keep investment costs low. Further market barriers for industrial heat pumps were identified by Arpagaus et al. 4, of which
  • deficits in presenting the limits of the heat pump cycle and its process integration,

  • future-proof working fluids and

  • lack of high temperature compressors

are addressed here by discussing specific thermodynamic cycles related to the compression heat pumps with solution circuit (CHPSC). The standard CHPSC is the so called Osenbrück cycle 8 shown in Fig. 3a, which requires at least two fluids, i.e., a refrigerant and a solvent. The unique characteristics of this cycle are a significant higher temperature glide during the approximately isobaric phase change of the internal working fluid mixture as compared to typical temperature differences of the external fluids in heat source and sink and, secondly, the contribution of exergy by mechanical energy using a compressor and a liquid pump, so that these cycles are not mistaken as an absorption heat pump, where exergy donation is related to heat. In practical applications the high temperature glide of the mixture leads to an evaporation and condensation, which stops respectively starts within the two-phase region. Thus, a liquid-gas separator below the evaporator is required. Based on Fig. 3a the process will be explained in the following. The vapor phase rich in refrigerant coming from the phase separator is compressed by a compressor and the solvent with a low refrigerant fraction by a liquid pump. Both streams are re-mixed before the condenser yielding a mass flow rich in refrigerant. Heat is transferred from the two-phase rich solution to the heat sink within the condenser during a combined process of condensing and absorbing until the mixture is saturated liquid. Then the rich solution is subcooled by the poor solution in the internal heat exchanger and expanded to low pressure entering the evaporator where heat is transferred from the heat source to the mixture. The internal heat exchanger is usually provided to enhance cycle efficiency. Compared to evaporator and condenser it is small sized due to the liquid-liquid design. When modifying this standard cycle one more general point has to be addressed according to Arpagaus et al. 4. The capability of a simple process integration, which excludes large additional heat flows at further temperature levels at the system boundary, as in some CHPSC cycles introduced by Ahlby 9 and Ziegler 10.

There exist several studies of thermodynamic modified cycles and different working fluid pairs for CHPSC 11, but up to now the limits of these cycles were not systematically investigated with respect to different cycle configurations, boundary conditions and technical limitations of current equipment. One extreme is to adapt a working fluid to a given cycle and its conditions. The other extreme is to adapt a cycle to a given working fluid, but this requires additional degrees of freedom, which arise as working fluid mixtures with high temperature glides are used. This latter strategy will be pursued here to present characteristic diagrams for potential users or vendors showing sink outlet temperature, heat pump temperature lift and some economically relevant parameters as volumetric heat capacity (VHC), heat transfer area ratio (HTA) and coefficient of performance (COP). The sink outlet temperature is defined as the temperature of the external fluid leaving the condenser towards the heat sink.

Ahrens et al. 11 published the most recent review about CHPSC and claimed NH3/H2O to be the most suitable working fluid pair for the CHPSC. The reasons for their choice are the amount of experimental experience already gained and the fact that both working fluids are natural, not highly flammable and without global warming potential (GWP) or ozone depletion potential (ODP). Further these substances do not create trifluoroacetic acid as an atmospheric breakdown product like R245fa, R365mfc, R1243zf, R1234yf or R1336mzz(Z) 12. This low environmental impact of NH3/H2O makes the mixture independent of future F-Gas regulations and interesting for industrial heat pumps. Pure NH3 is already used in standard compression cycles up to 90 °C and the mixture NH3/H2O is used in the Osenbrück cycle with two-stage compression up to 120 °C 4. Within the above-described cycle with one stage compression this mixture achieves temperatures up to 111 °C, when constrained by a 28 bar pressure limit and a maximal compressor discharge temperature (CDT) of 170 °C 13.

Brunin et al. 14 theoretically dealt with the standard cycle, but used an oil cooled screw compressor, in which the compressed gas gets cooled by a surplus of lubrication oil, after compression oil and refrigerant where separated and the oil is cooled by the poor solution and passed back into the compressor, see Fig. 3b. The high-pressure limit was set to 20 bar. The temperature glides of heat source and sink were fixed to 10 K. By keeping in mind that the efficiency of the Lorenz cycle increases in comparison to the Carnot cycle, when higher temperature glides are on hand, this choice resulted in a narrow segment of the entire characteristic diagram of the CHPSC cycle. In addition, at low temperature glides, the Lorenz cycle passes into the Carnot cycle making the CHPSC unattractive because the specific enthalpy differences in the heat exchanger tend to zero and had to be compensated be high mass and volumetric flows. The studied oil cooling is a beneficial solution to reduce the excessive CDT of ammonia and water, which are an open challenge also for other working fluids as mentioned by Arpagaus et al. 4. Due to their high isentropic heating rate,
urn:x-wiley:0009286X:media:cite202200111-math-0003(2)

both natural working fluids heat up at a rate of about 8 K bar−1 whereas for synthetic refrigerants, as R1336mzz(Z) or R245fa, this rate is about 3 K bar−1.

Further studies of the Osenbrück cycle by Jensen et al. 13, 15 introduced a gas cooler below the compressor and raised the high pressure limit to 28 bar and 52 bar. The maximal CDT was fixed to 170 °C. Likewise their study dealt with a narrow segment fixing the temperature glide at the sink to 20 K and the temperature lift of the heat pump to 25 K. Their results were presented in relation to internal parameters of the cycle making them hardly accessible to non-specialists. In a parallel investigation by the same group of authors 16 this drawback was overcome by using sink outlet temperature and heat pump temperature lift to present their results. Brunin et al. 14 and Jensen et al. 16 defined the temperature lift as
urn:x-wiley:0009286X:media:cite202200111-math-0004(3)
In general, this is not erroneous as long as the temperature glides in sink and source are equal and small, but if they become asymmetric and larger, this definition has to be replaced by
urn:x-wiley:0009286X:media:cite202200111-math-0005(4)

to correctly compare cycle efficiency with different temperature glides and lifts. Two pressure levels, 28 bar and 50 bar, and a maximal CDT of 180 °C were considered in 16. The additional degrees of freedom were fixed by an economically optimization. After converting the results of Brunin et al. 14 and Jensen et al. 16 to the same temperature lift, Eq. 4, the working domains (WD) of the low-pressure cycles are combined in Fig. 2a and the high-pressure results of Jensen et al. 16 are shown in Fig. 2b. Their curves were extrapolated linearly, when cut off by their constraint Tsnk,in < Tsrc,in, since ΔTlif is still positive. Two limits are dominant in the data from Jensen et al. 16. Firstly, the violation of the self-imposed limit Tsrc,out > 0 °C, which is the part with positive slope, and secondly the maximal CDT in all other cases. The WD as calculated by Brunin et al. 14 are limited by the curve with positive slope standing for a low-pressure limit of 1 bar, the constant or slight positive slope is due a restriction in minimal COP of 4 and at 140 °C the high-pressure limit of 20 bar is limiting.

Details are in the caption following the image
WD of the CHPSC for different high pressure limits and temperature glides at source and sink.

The highest temperature at sink outlet is 140 °C for all cases, but the maximal temperature lift for the standard cycle starts to decrease for temperatures higher than 90 °C for the low-pressure components and at 115 °C for the high-pressure components. In contrast the lift remains nearly constant for the oil cooled screw compressor up to 140 °C.

The current studies show that slight modifications of the CHPSC cycle, especially the path of gas compression, have a great impact on cycle's WD. The most significant constraint arises from the CDT. Constraints chosen by Brunin et al. 14 and Jensen et al. 16 are different and arbitrary, for example the COP limit, so that special care is needed if their results are compared. Due to the additional degrees of freedom by using wide-boiling mixtures, the working domain of the working fluid mixture may be adjusted by cycle modifications as will be presented in this study. Besides the technical limits, economic parameters had not been compared in a basic way so far, but these parameters are also important for decision making if a working fluid is suitable or not. R1336mzz(Z) serves as benchmark working fluid because the industry is more familiar with standard compression heat pump cycles with pure working fluids and this substance is a fluid under investigation which do not operate in vacuum, is not flammable, suitable for high temperatures up to 150 °C and is excluded from current F-Gas regulations 4.

This article initially deals in Sect. 2 with the selection of thermodynamic cycles. It follows a detailed description of the chosen technical constrains for all used devices. Sect. 4 is about the thermodynamic model and the developed algorithm and which software is used. Results about the working domains are found in Sect. 5 and the final Sect. 6 is the conclusion.

2 Selection of Thermodynamic Cycles

The WD of the standard Osenbrück cycles in Fig. 3a, here called STD25 and STD40 with the letters representing the upper high-pressure limit, and the standard Osenbrück cycle including an oil cooled compressor in Fig. 3b were investigated so far 14, 16. STD25 is part of this investigation due to different constraints versus Jensen et al. 16 and also for comparison purposes. STD40 with a 40 bar limit is added in contrast to the 50 bar limit of 16 because a standardized industrial pressure level is 40 bar. The WD of the cycle in Fig. 3b investigated by Brunin et al. 14 is only limited by the definition of the CDT and the maximal pressure difference and it has been shown that this cycle is theoretically suitable for sink temperatures up to 150 °C so that it is not part of this study since little additional information would be added. As the previous studies had shown the limit of using NH3/H2O is a result of the CDT limit. So, two additional cycles were selected in Fig. 3c and 3d, were the CDT is lowered by a wet compression (WETC) or by two two-stage compression cycles with intercooling but different constraints concerning the compressors. 2STPP deals with an equal pressure ratio of the compressors and 2STTT with an equal CDT. The cycle in Fig. 3c is the same for the benchmark fluid R1336mzz(Z), but with the difference that the refrigerant gets fully evaporated. All these cycles except STD40 deal with a high-pressure limit of 25 bar.

Details are in the caption following the image
Investigated CHPSC cycles. a) Osenbrück, b) oil-cooled screw compressor, c) wet compression and d) two-stage compression.

In WETC the working fluid mixture flows completely through the compressor. Strictly speaking it is not a CHPSC cycle due to the missing solution circuit, but a promising solution to lower CDT, as the liquid absorbs some of the emerging thermal energy during compression. This cycle was theoretically compared to wet compression of pure working fluids by Itard 17 and later experimental investigated by Zaytsev 18 and Infante Ferreira et al. 19. An internal heat exchanger is introduced here, which significantly increases the efficiency and also circumvents technical limitations of the compressor. The two-stage compression cycles with intercooling were theoretical and experimental investigated by Nordtvedt 20. By the use of two compressors each compressor has to overcome a lower pressure ratio and the intercooler lowers the inlet temperature of the second compressor.

3 Model Constraints

Most parameters are basically affected by costs, whereas some parameters as the maximal oil-temperature have a physical origin due to chemical decomposition or inadequate viscosity. The temperature range of heat source and sink are orientated at the inquiry of the cumulative waste heat and process heat by Marina et al. 5, cf. Fig. 1. The investigated temperature range is therefore 20 °C to 150 °C.

The temperature glides at source and sink were calculated at 5 K, 10 K, 20 K and 40 K but are hold constant at source and sink to reduce the parameter space. This assumption lowers the total WD for higher temperature glides, as data from Jensen et al. 16 for 20/20 K and 20/10 K in Fig. 2 had shown.

3.1 Compressor

Compressors have a major impact on the WD and efficiency of heat pumps. There exist many different compressor types with individual characteristics. Mostly reciprocating piston and oil cooled twin-screw compressors are used for heating capacities below 10 MW 4 and are obtainable for NH3. Therefore, only these both types are considered in this work. The wet compression cycles are only conceivable with a screw compressor. Tab. 1 lists typical technical limits and parameters of both types.

Table 1. Compressor limits.

Limit

Wet screw

Reciprocating piston

ϑout,max [°C]

1) 300°C−ϑi

2) 180

180

Δpmax [bar]

12

pin,max [bar]

10

pout,max [bar]

25

25 bar/40 bar

ηs [–]

0.874–0.0135 π

0.874–0.0135 π

λ [–]

0.9625–0.0108 π

0.975–0.025 π

  • a) Rotor deformation,
  • b) oil decomposition,
  • c) costs,
  • d) Brunin et al. 14,
  • e) NH3 twin-screw 22,
  • f) study of 56 compressors 21.

To not favor a specific pressure ratio, the build in volume ratio of the compressors is assumed to be variable so that isentropic and volumetric efficiencies follow the pressure ratio linearly. This choice will raise the efficiency of the cycles towards low pressure ratios. The screw compressors have two temperature limits, the first one is due to the temperature gradient across the rotors and the second one due to the applied oil. The maximal discharge temperature for reciprocating piston was set to 180 °C, which is 20 K above an experimental proofed limit of 160 °C 20. The isentropic efficiency is an important parameter but depend on other parameters like capacity or rotational speed. The function applied by Brunin et al. 14 is between the best 20 % of Edler's 21 study on semi-hermetic piston compressors of small capacity (< 200 m3h−1) and the data of an unspecified NH3 twin-screw compressor 22. Therefore, for both compressor types the function of Brunin et al. 14 will be applied to the simulation models. For wet compression the volumetric efficiency is the same as for the reciprocating piston compressor because no experimental proof for wet screw compressors for this special purpose exists so far and the experiments by Zaytsev 18 revealed open challenges concerning the sealing of the working clearances of the rotors.

3.2 Heat Exchanger

Different methods to compare condenser and evaporator between CHPSC and standard compression cycles was discussed by Hultén et al. 23. Since the technical WD are of interest, the same pinch points (PP) are used. The secondary fluid in source and sink is liquid water pressurized to 10 bar. So, temperatures below 0 °C were excluded by this assumption, although the cycle might be capable providing these temperatures. Internal heat exchangers typically increase the WD, the smaller their PP is.

To estimating the HTA, constant thermal transmittances for evaporation, condensation, a mixing of both and one phase heat exchange are assumed for both working fluids. Due to high deviations between different heat transfer correlations for pure refrigerants during condensation and evaporation of up to 300 % 24, a detailed calculation of the heat transfer is not undertaken, instead averaged and estimated values are used.

One-phase liquid heat transfer coefficients are assumed as 5000 W m−2K−1 20 and for one-phase gas flows as 250 W m−2K−1. Averaged heat transfer coefficients for condensing, 1900 W m−2K−1, and evaporating, 2200 W m−2K−1, of pure working fluids were averaged from correlations for hydrofluorocarbon and hydrofluoroolefin presented by Shon et al. 25 and Eldeeb et al. 24. No distinction is made if the working fluid is superheated or subcooled. For NH3/H2O some experimental studies on heat transfer were summarized by Ahrens et al. 11. The deviations and also the absolute U-values have the same order of magnitude as for pure fluids, but in relation to each other, the additional mass transport of the mixture during phase change is considered here, which lead to lower heat transfer coefficients for condensation, 1400 W m−2K−1, and evaporation, 2000 W m−2K−1. By neglecting the portion of heat conduction through the wall between the fluids, U-values were calculated by Eq. 5 and summarized in Tab. 2.
urn:x-wiley:0009286X:media:cite202200111-math-0006(5)

These values are significantly lower compared to Jensen et al. 16 and Ommen et al. 26 except for pure refrigerant evaporation, but for NH3/H2O in accordance with experiments 20.

Table 2. U-values for NH3/H2O and R1336mzz(Z) in different heat exchanger configurations.

U [W m−2K−1]

NH3/H2O

R1336mzz(Z)

evaporator

1400

1500

condenser

1100

1400

internal heat exchanger (liquid/liquid)

2500

internal heat exchanger (liquid/evaporator)

1400

internal heat exchanger/intercooler (gas/liquid)

250

250

3.3 Other Devices

For heat exchangers, expansion valves, gas-liquid separators and liquid pumps only the maximal pressure limit is set to 25 bar or 40 bar. The minimal low pressure is 1 bar to avoid inert gases to enter.

4 Thermodynamic Model

The thermodynamic model is based on the steady mass Eq. 6, component Eq. 7, energy Eq. 8 and entropy balances Eq. 9 of each device.
urn:x-wiley:0009286X:media:cite202200111-math-0007(6)
urn:x-wiley:0009286X:media:cite202200111-math-0008(7)
urn:x-wiley:0009286X:media:cite202200111-math-0009(8)
urn:x-wiley:0009286X:media:cite202200111-math-0010(9)
To compare and evaluate the different cycles three parameters are selected:
urn:x-wiley:0009286X:media:cite202200111-math-0011(10)
urn:x-wiley:0009286X:media:cite202200111-math-0012(11)
urn:x-wiley:0009286X:media:cite202200111-math-0013(12)

While the first parameter is an indicator for the operational costs, HTA and VHC are representatives for the investment costs.

4.1 Compressors

The isentropic efficiency, Eq. 13, is used to determine the enthalpy difference of the compressors.
urn:x-wiley:0009286X:media:cite202200111-math-0014(13)

The compressors are adiabatic. Isentropic and volumetric efficiency follow the equations in Tab. 1. The two-stage compression cycle has additional degrees of freedom and is treated in two different ways. In one case the pressure ration and in the other case the CDT of both compressors is equal.

4.2 Heat Exchangers

All heat exchangers are assumed isobaric, in counter flow with a PP of 5 K. Condensation stops at the saturated liquid curve and evaporation of R1336mzz(Z) at the state of saturated vapor. The PP locations are summarized in Tab. 3.

Table 3. Positions of PP.

NH3/H2O

R1336mzz(Z)

evaporator

forced to cold side

cold side

condenser

forced to hot side

saturated vapor

internal heat exchanger (liquid/liquid)

hot side

internal heat exchanger (liquid/evaporator)

cold side

internal heat exchanger/intercooler (gas/liquid)

cold side

cold side

Details are in the caption following the image
Algorithm to determine all internal parameters of the mixture within the condenser on the basis of sink mean temperature, sink temperature difference, high pressure and PP.
Due to the composition of the mixture and the circulation ratio of the solution circuit additional degrees of freedom arise. By fixing the high pressure to its highest limit, Eq. 14, one degree is reduced. The condensation temperature of pure ammonia at 25 bar is 58.2 °C and at 40 bar is 78.4 °C. If Tsnk,in is below these temperatures, ph,max has to be lower for the mixture to remain in the two-phase region following
urn:x-wiley:0009286X:media:cite202200111-math-0015(14)
Still ξmix, urn:x-wiley:0009286X:media:cite202200111-math-0016 and the enthalpy at both sides of the condenser remain as unknowns. These parameters are calculated with the help of an algorithm, whose program flow chart is shown in Fig. 4. Sink heat flow urn:x-wiley:0009286X:media:cite202200111-math-0017, sink mean temperature Tm,snk and sink temperature difference ΔTsnk are predetermined as they represent the general task of the heat supply. In the first iteration loop temperature, enthalpy and entropy at the inlet and outlet plus the mass flow of the secondary fluid of the sink are calculated to a specified tolerance. In the main routine the number N of parts of which the heat exchanger is divided into, the pinch point temperature difference ΔTpp and the high pressure are predetermined. As the temperature profiles are continuous N has not to exceed a value of 20. The temperature profiles of both streams are calculated by fixing the temperature difference between both streams at the cold and hot end of the condenser to the previous defined value. A maximal value for the mass fraction of the strong solution urn:x-wiley:0009286X:media:cite202200111-math-0018 is calculated as well. It is defined by the high pressure and the minimal temperature of the mixture in a state of saturated liquid at the cold side of the condenser. In the second iteration loop the condition of a fixed temperature difference at the cold side is dropped and the mass fraction is lowered step by step until every temperature difference between both streams along the condenser is greater than 5 K. The lowering of the mixture's mass fraction in general results in a change of the shape of the temperature profile from concave to convex, so that the temperature difference of the mixture gets smaller compared to the external fluid. If the second iteration loop was successfully solved to a specific tolerance, the algorithm has calculated the mass fraction, the mass flow of the rich solution as well as the enthalpy and entropy of the mixture at both sides. Due to the coupling of the specific enthalpy difference of condenser and evaporator via
urn:x-wiley:0009286X:media:cite202200111-math-0019(15)

the slope of the internal temperature profile in the evaporator is smaller so that this algorithm indirectly solves the PP problem within the evaporator, if the external temperature glides are symmetric, see Fig. 5. If the high pressure is fixed at its technical limit the low pressure level is raised too. This circumstance is beneficial for COP and VHC as ν decreases with higher pressure. Further the pressure ratio decreases increasing the COP and decreasing the CDT.

Details are in the caption following the image
Typical temperature profiles in condenser and evaporator determined by the algorithm. The temperature profiles of source and sink were predetermined, the internal temperature profiles are the result of the algorithm.
The required total surface of a single heat exchangers is
urn:x-wiley:0009286X:media:cite202200111-math-0020(16)

where Tm,i are the thermodynamic mean temperatures of both fluid streams calculated by the exact solution in Eq. 4.

4.3 Other Devices

No pressure losses are considered. The solution pumps are reversible. The expansion valves isenthalpic. Separators are adiabatic and the entering and leaving mass flows are equal in pressure and temperature.

4.4 Simulation Environment

The system of equations and individual procedures for each cycle are separately put in an own subroutine of the software engineering equations solver (EES) V10.836-3D. A mesh for Tm,snk and Tm,src with 2.5 K steps is prepared and solved via the parametric table property. Tm,src and Tm,snk start with the lowest values. At first Tm,snk is increased until a defined maximum is reached, then Tm,snc is increased by one step and Tm,snk is decreased to ΔTlif = 2.5 K. This method results in a maximum of 1200 calculations per cycle and individual temperature glide. The resulting waveform is crucial for convergence although the guess values are updated after each successful calculation, because it prevents large steps in ΔTlif. The property data of NH3/H2O is calculated with the help of the external library AWMix 1.0, which includes a Helmholtz Free Energy equation of state developed by Tillner-Roth et al. 27. Property data of R1336mzz(Z) is supplied by EES.

5 Results

In Figs. 6a–d the WD of the cycles STD25, R1336, WETC and 2STTT for four symmetric temperature differences at source at sink between 20 °C and 150 °C are shown. This range is chosen to cover the investigated temperature range by Marina et al. 5. The WD of pure NH3 in a classic compression cycle constrained by a high-pressure limit of 40 bar is added to the figures to outline that above 70 °C to 85 °C CHPSC cycles are able to retain NH3 as working fluid. CHPSC cycles with NH3/H2O are able to operate below this temperature range as well, but the industrial heat demand is negligibly below 60 °C, cf. Fig. 1. As STD40 do not significantly extend the WD compared to STD25, see the detailed results in Figs. S9–S12 in the Supporting Information, and 2STPP is inferior towards 2STTT, Figs. S21–S24, both cycles are excluded from Figs. 6a–d. All the detailed results involving symmetric temperature differences of 5 K, 10 K, 20 K and 40 K at sink and source and the cycles STD25, STD40, R1336, WETC, 2STTT and 2STPP containing the WD, COP, HTA and VHC are given in Figs. S1–S24.

Details are in the caption following the image
WD of the investigated cycles for a) 5 K, b) 10 K, c) 20 K and d) 40 K symmetric temperature glide at sink and source. The minimal temperature lift calculated from the investigation of Marina et al. 5 is added.

In all cases 2STTT and WETC match the WD of R1336. High temperature lifts up to 85 K are attained by these NH3/H2O cycles, but only WETC is able to provide urn:x-wiley:0009286X:media:cite202200111-math-0021 up to 150 °C. STD25 reaches 150 °C but without a considerable temperature lift at any ΔTsnk. 2STTT and R1336 come below urn:x-wiley:0009286X:media:cite202200111-math-0022 at about 130 °C. In comparison to the reference R1336 the WD are contrary due to the sub atmospheric vapor pressure of R1366mzz(Z) at low temperatures. While the temperature lifts of R1336 and 2STTT decrease towards 150 °C because of the CDT limit, WETC is not affected by the CDT limit. A detailed comparison of these cycles is given in Fig. 7 for ΔTsnk = 10 K, which is closer to the Carnot cycle and therefore beneficial for R1336.

Details are in the caption following the image
Detailed results of a) R1336, b) WETC and c) 2STT between 95 °C and 150 °C and 10 K temperature glide at sink and source.

If temperature lifts are greater than 20 K the COP is about one point lower for both NH3/H2O cycles. The HTA in relation to R1336 is twice as large for 2STT and 1.7 times for WETC. The course of the VHC curves is different between the pure working fluid and the mixtures. Due to the change in composition and therefore nearly constant pressures the VHC depends on Tsnk,out weakly, whereas a linear relation is found for R1336 making a direct comparison subject to Tsnk,out. The turning point is at about 130 °C as from where the VHC of R1336 becomes greater. At temperature lifts of about 60 K the VHC of WETC falls below 1000 kJ m−3, while it is 2000 kJ m−3 for 2STTT. R1336 in a single compression cycle is not capable of these temperature lifts.

If ΔTsnk is raised to 20 K and 40 K, cf. Figs. S3, S4, S15, S16, S19 and S20, the COP of both NH3/H2O cycles increases and at 40 K is at about one point higher than R1336. The HTA also decreases to be slightly greater than for R1336 at 40 K where the VHC of WETC and 2STTT is always greater than of R1336. Although it is often highlighted in literature that the temperature profiles in evaporator and condenser are matching better for working fluids approaching the Lorenz cycles, thus leading to less entropy production in these devices, the overall performance of the cycle towards a pure working fluid becomes just higher at about 20 to 30 K in the case of NH3/H2O and the cycles STD25, STD40, 2STTT, 2STPP and WETC.

6 Conclusion

This systematic simulation study has shown that the use of NH3/H2O in high temperature heat pumps with considerable temperature lift and sink flow temperature up to 150 °C opens a large potential for waste heat usage in EU28 industry. Dry compressors in the Osenbrück cycles at pressures limits of 25 bar and 40 bar are indeed only suitable up to 120 °C as was stated by Jensen et al. 16. Two-stage intercooled or wet compression cycles are necessary to significantly overcome the limiting compressor discharge temperature (CDT) of the standard Osenbrück cycle. But above 130 °C, the temperature lift between waste and process heat increases in a way only wet compression is able to deal with. In comparison to R1336mzz(Z) the heat transfer area ratio (HTA) of NH3/H2O is about 1.5–2 times larger, but the COP and volumetric heat capacity (VHC) values are comparable within the working domain (WD) of R1336mzz(Z). The symmetric conditions for ΔTsnk and ΔTsrc chosen here, allow some minor space for a further extension of the WD. Especially ΔTsrc might not be fixed, but since the other constrains were already technically limited, it is questionable if all parameters like WD, COP, VHC and HTA may be maximized simultaneously.

Additional equipment for the two-stage cycles as liquid pump and separator has to be taken into account when costs are specified. These costs are not being tracked by the evaluation parameters. However, the wet compression cycle is simpler and performs likely the two-stage cycles except when it comes to the VHC. The implementation of wet compression is possible with modified screw compressors, whose differential pressure may not exceed 12 bar as was considered here, but these compressors are not commercially available contrary to two-stage compressions cycles, which are already distributed.

This investigation did not consider all compression heat pump with solution circuit (CHPSC) variants and only the temperature range between 20 °C to 150 °C was evaluated. The lift of the investigated cycles at lower temperatures might be higher and the full potential of NH3/H2O in simple thermodynamic cycles needs to be further analyzed.

Supporting Information

Supporting Information for this article can be found under DOI: https://doi.org/10.1002/cite.202200111. This section includes 24 figures with detailed results of each simulation.

Acknowledgements

Open access funding enabled and organized by Projekt DEAL.

    Symbols used

  1. A [m2]
  2. area

  3. h [kJ kg−1]
  4. mass specific enthalpy

  5. urn:x-wiley:0009286X:media:cite202200111-math-0023 [kg s−1]
  6. mass flow

  7. N [–]
  8. number

  9. P [kW]
  10. power

  11. p [bar]
  12. pressure

  13. urn:x-wiley:0009286X:media:cite202200111-math-0024 [kW]
  14. heat flow

  15. q [kJ kg−1]
  16. mass specific heat

  17. urn:x-wiley:0009286X:media:cite202200111-math-0025 [kW K−1]
  18. rate of entropy production

  19. s [kJ kg−1K−1]
  20. mass specific entropy

  21. T [K]
  22. absolute temperature

  23. U [W m−2K−1]
  24. thermal transmittance

  25. ν [m3kg−1]
  26. specific volume

  27. Greek letters

  28. α [W m−2K−1]
  29. heat transfer coefficient

  30. ζ [–]
  31. Carnot efficiency

  32. η [–]
  33. efficiency

  34. ϑ [°C]
  35. Celsius temperature

  36. Λ [K bar−1]
  37. isentropic heating rate

  38. λ [–]
  39. volumetric efficiency

  40. ξ [–]
  41. mass fraction

  42. π [–]
  43. pressure ratio

  44. Sub- and Superscripts

  45. saturated liquid

  46. 1, 2, …
  47. numerical index

  48. C
  49. condenser

  50. CP
  51. compressor

  52. d
  53. difference

  54. E
  55. evaporator

  56. h
  57. high

  58. HE
  59. heat exchanger

  60. I
  61. variable numerical index

  62. in
  63. entering

  64. irr
  65. irreversible

  66. l
  67. low

  68. lif
  69. lift

  70. lit
  71. literature

  72. m
  73. mean

  74. max
  75. maximal

  76. min
  77. minimal

  78. mix
  79. mixture

  80. out
  81. leaving

  82. pp
  83. pinch point

  84. s
  85. isentropic

  86. snk
  87. sink

  88. src
  89. source

  90. SP
  91. solution pump

  92. tot
  93. total

  94. Abbreviations

  95. CDT
  96. compressor discharge temperature

  97. CHPSC
  98. compression heat pump with solution circuit

  99. COP
  100. coefficient of performance

  101. EES
  102. engineering equation solver

  103. EU28
  104. 28 member states of the European Union

  105. GWP
  106. global warming potential

  107. HTA
  108. heat transfer area ratio

  109. ODP
  110. ozone depletion potential

  111. PP
  112. pinch point

  113. VHC
  114. volumetric heat capacity

  115. WD
  116. working domain

    • The full text of this article hosted at iucr.org is unavailable due to technical difficulties.