Volume 2025, Issue 1 5975734
Research Article
Open Access

An Improved Communication-Free Dual Characteristic Over Current-Based Protection Scheme for AC Microgrids

Hossein Mohammadi Panah

Hossein Mohammadi Panah

Department of Power and Control Engineering , School of Electrical and Computer Engineering , Shiraz University , Shiraz , Iran , shirazu.ac.ir

Search for more papers by this author
Behrooz Zaker

Corresponding Author

Behrooz Zaker

Department of Power and Control Engineering , School of Electrical and Computer Engineering , Shiraz University , Shiraz , Iran , shirazu.ac.ir

Search for more papers by this author
Haidar Samet

Corresponding Author

Haidar Samet

Department of Power and Control Engineering , School of Electrical and Computer Engineering , Shiraz University , Shiraz , Iran , shirazu.ac.ir

Search for more papers by this author
First published: 10 July 2025
Academic Editor: Paulo Moisés Almeida Costa

Abstract

The entry of distributed generation causes the network to become complicated, and as a result, the protection coordination between the network equipment is lost. In previous studies, three decision variables were considered for each directional overcurrent relay: time dial setting in the main mode, time dial setting in the backup mode, and pickup current (Ip). However, the minimum coordination time interval between the main and backup relay was lost. In this paper, communication-free dual characteristics directional overcurrent relays are used, considering six decision variables: Ip, time dial setting of the relays in the main and backup mode, breakpoint current, and the type of curves in main and backup operations. The proposed scheme maintains the minimum time interval between the main and backup relays, which reduces the operation time of the relays compared to previous studies. The proposed scheme is implemented on the modified IEEE 30-bus network distribution section. DIGSILENT software is used for simulation, and load currents and fault currents of protection relays in grid-connected and islanded conditions are extracted based on load flow and short circuit studies. Then, the optimization problem is solved using the genetic algorithm in MATLAB software, and optimal settings are obtained to minimize the operation time of the relays. The simulation results of the proposed method shows that the operation time of the relays can be improved by 17% compared with the previous existing method.

1. Introduction

Microgrids will have many benefits for both consumers and electricity production companies; from the perspective of consumers, microgrids can simultaneously provide electricity and heat, increase reliability, reduce greenhouse gas emissions, and improve quality, and from the perspective of companies, the use of microgrid electricity has the potential to reduce consumption demand as well as reduce the facilities for the development of transmission lines and eliminate peak load, which also reduces network losses [1, 2]. Despite all the advantages of microgrids in the presence of distributed generation (DG), there are possible adverse effects on the distribution network, which include complicating the network and, as a result, the development of the network protection system and the operation and coordination of the network protection relays are associated with problems. Connecting DGs to the network causes harmonics and reduces short-circuit impedance. Also, when DGs enter distribution networks, these networks lose their radial structure. Therefore, due to the circularization of the distribution network, to detect the direction of the fault current, relays that operate based on the direction of the fault current are needed [3, 4]. Directional over current relays (DOCRs) can detect current direction by measuring current, voltage, and angle between current and voltage. This equipment recognizes the direction of the power passing through the line and only issues permission to pass the power in a specific direction.

A protection plan aims to isolate the faulty parts from the healthy parts and minimize the consequences of the faults by reducing the operating time of the protective equipment. However, coordinating protective relays is challenging [5, 6].

In recent years, different methods have been proposed to solve the coordination problem of protection relays in microgrids. These methods can be divided into two general categories [7, 8].
  • 1.

    Methods based on the communication system

  • 2.

    Methods without the need of the communication system

The communication system-based methods usually use adaptive protection, which uses communication links to change the settings. In [8], the protection coordination scheme for microgrids using DOC relays with dual settings and with the help of a communication platform has been presented. In this scheme, both relays in one line are connected with each other. The possibility of cyber-attacks and loss of the communication link, which leads to failure of the relay’s functionality, are the main disadvantages of this method. In [9, 10], an adaptive protection scheme has been proposed to identify the fault areas and achieve coordination between relays. This method requires a lot of measurements, such as the voltage and current of all DGs. In [11], the authors have utilized intelligent electronic devices and a communication channel to obtain real-time system information to update relay settings. This method was implemented in distribution networks with dynamically changing operating conditions, which include loss of loads, generations, and lines. A review of communication failure impacts on adaptive microgrid protection schemes has been carried out by authors in [12].

The second category includes methods that do not require a communication system, which establishes coordination between relays through local measurement. In [13], a communication-free protection coordination scheme of DOC relays with dual settings and voltage-dependent protection characteristics has been presented. This design adds a voltage characteristic to the relay operation time relationship. Among its disadvantages is the ineffectiveness of the presented plan for faults with high currents. In [14], a scheme for protection coordination for microgrids using DOC relays with dual settings and without the need for a communication platform has been presented. One of the advantages of using the double characteristic curve is the reduction of the operation time of the relays, but the disadvantage of the mentioned method is the loss of the minimum coordination time interval (CTI) between the main and backup relays. Some studies have presented protection schemes that do not use IEEE and IEC standard curves for synchronizing relays. For example, in [1517], designs using nonstandard characteristics for DOC relays have been presented. The advantages of using nonstandard curves are higher flexibility and accuracy, while the disadvantages are increased cost, complexity, and networking to coordinate relays, which is not practical in reality. Another approach that does not require the communication system is using fault current limiters (FCLs) to coordinate relays [1820]. However, using FCLs has some disadvantages, such as the complexity of finding the optimal locations to install FCLs, and the increase in costs. In [2123], metaheuristic optimization methods have been used for communication-free protection coordination of DOC relays. The objective functions of these studies have only considered the reduction of the total operation time of the main relays. Therefore, as a disadvantage, the operation time between the main and backup relays was not optimal. One of the most recent works in the field of coordination relays without a communication platform is [24]. Three decision variables have been considered for each DOCR, which include time dial setting in main mode (TDSPm) and time dial setting in backup mode (TDSbk) and pickup current (Ip). As shown in Figure 1(a), the proposed dual characteristic scheme consists of two protection curves: the Very Inverse (VI) curve for the main function and the Normal Inverse (NI) curve for the backup function. There is also a breakpoint (IH) where the two curves, VI and NI, are connected. The use of a combination of NI and VI curves in all relays has led to the loss of the CTI between the main and backup relays, which is the main drawback of this study.

Details are in the caption following the image
(a) Protection characteristic curve in [24]. (b) Proposed protection characteristic curve.
Details are in the caption following the image
(a) Protection characteristic curve in [24]. (b) Proposed protection characteristic curve.

In this paper, an attempt is made to eliminate problems such as the loss of CTI that existed in [24]. In Figure 1(b), the proposed communication-free dual characteristic coordination scheme is shown. The curve is divided into two parts, which include the characteristic curves of types 1 and 2. The type-1 characteristic curves are used for relay operation in the backup mode, and their slope will be less than or equal to that of type-2 curves. The optimization algorithm selects the type of curve from NI and VI curves. The type-2 characteristic curve is used for relay operation in the main mode, which has a higher slope and shorter operation time, and the type of curve is selected by the optimization algorithm from NI, VI, and Extremely Inverse (EI) curves. Therefore, in the proposed method, six decision variables are considered for the ith DOCR, which include (, , Ip, IH, and main and backup curves).

A comparison between the previous studies and the proposed method of this paper is presented in Table 1. For evaluation, the following questions are asked and answered:
  • Q1. Do the relays have dual characteristics?

  • Q2. Have adaptive protection measures been used for coordination?

  • Q3. Have FCLs been used?

  • Q4. Has the characteristic curve selection been optimized?

  • Q5. Have both modes of operation (grid connected and islanded) been considered in the coordination scheme?

  • Q6. Has the breakpoint of the characteristic curve been optimized?

  • Q7. Do the relay settings include all symmetrical and unsymmetrical faults?

Table 1. Comparison of the previous methods.
Reference Category Q1 Q2 Q3 Q4 Q5 Q6 Q7
Reference [8] With communication Yes No No No Yes No No
Reference [9] No Yes No No Yes No No
Reference [10] Yes Yes No No Yes No No
Reference [11] No Yes No No No No No
Reference [13] Communication free Yes No No No Yes No No
Reference [14] Yes No No No Yes No No
Reference [17] No No No Yes Yes No No
Reference [18] No No Yes No Yes No No
Reference [24] Yes No No Yes Yes No No
Proposed method Yes No No Yes Yes Yes Yes
  • Note: The last row of Table 1 indicate the contributions of this paper compared to the previous studies (other rows).
Among the innovations of the proposed coordination scheme compared with existing coordination schemes, the following can be mentioned:
  • Improving the performance of the protection system by optimizing the IH.

  • The use of different curves for the performance of each relay in the main and backup modes, which is obtained by the optimization algorithm.

  • The obtained settings for the relays are valid for both modes of operation (grid connected and islanded), and there is no need to change the settings when the operating mode is changed.

  • Providing optimized relay settings for both symmetrical and unsymmetrical faults and for both modes of operation (grid connected and islanded).

2. Proposed Protection Coordination Scheme

Despite of many previous studies in which the optimal settings of the relays have just given for the grid-connected mode or islanded mode, in the proposed coordination scheme, the optimal settings are provided for both grid-connected and islanded operation modes. In this section, the decision variables are defined in the first subsection. In the second subsection, the objective function is described and then the constraints of the problem and their limits are defined. Thereafter, the optimization algorithm, the number of decision variables, and the problem-solving flowchart are explained next.

2.1. Decision Variables

In GA, decision variables are one of the main components of optimizing the objective function. By accurately and appropriately defining these variables, we can reduce the relay’s operation time and maintain the CTI between the main and backup relays. In the proposed method, six decision variables are proposed for each relay, including the following, and their optimal values are determined during the problem-solving process.
  • 1.

    (TDSPm)

  • 2.

    (TDSbk)

  • 3.

    Ip

  • 4.

    Break point current (IH)

  • 5.

    Main protection curve

  • 6.

    Backup protection curve

2.2. Objective Function

In most of the previous studies, objective functions were considered to reduce the operation time of the relays in the optimization algorithm. In [15, 2123], the aim of the objective function is only the reduction of the total operation time of the main relays. In previous studies, the objective function for reducing the operation time of relays in both symmetrical and unsymmetrical faults has not been presented for both modes of operation (grid connected and islanded). Therefore, considering the difference in the nature of faults (symmetrical and unsymmetrical faults), two objective functions are proposed, which are presented in Sections 2.2.1 and 2.2.2.

2.2.1. Objective Function for Symmetrical Faults

The objective function for symmetrical faults in this paper is defined as equation (1) to reduce the operation times of main and backup relays in grid-connected and islanded modes to achieve higher reliability. In the optimization process, the CTI between the main and backup relays may be lost. One common method for maintaining CTI is to use penalty methods. Therefore, as shown in equation (1), a penalty term is added to the objective function to ensure that the CTI is not lost at any fault location.
()
()

In equation (1), the symbols nc, nf, npm, and nbk indicate the number of different operating modes (grid-connected and islanded), number of fault locations, number of main relays, and number of backup relays, respectively. is the time of operation of the ith main relay for cth operating mode at jth fault location. is the time of operation of the kth backup relay for cth operating mode at jth fault location. When the time difference between the backup relay and the main relay for the jth fault location is more than CTI, the penalty function in equation (1) returns zero, as shown in equation (2). Also, when the time difference between the backup relay and the main relay for the jth fault location is less than CTI, the penalty function in equation (1) returns δ. δ is a big value, and in the proposed method, it is considered equal to 100. CTI usually takes a value between 0.2 and 0.5 s, which in this paper is set to be 0.2 s.

2.2.2. Objective Function for Symmetrical and Unsymmetrical Faults

Considering that in reality most of the faults are unsymmetrical, solving the problem by only considering symmetrical faults in the objective function may lead to longer performance times for unsymmetrical faults. Therefore, in equation (3), four objective functions are considered for three-phase, two-phase, two-phase-to-ground, and single-phase-to-ground faults. At the end, the total objective function, which is the summation of these four, is optimized.
()

2.3. Constraints

The following constraints are considered in the optimization procedure to ensure having a reliable operation.

2.3.1. Ip

The first constraint that is considered in the proposed plan is the upper and lower limits for the Ip of the relay based on equation (4). The lower limit of the pickup current of the ith relay (IP,i) is determined based on the fact that normally the relay does not operate when the load current passes through it, so its lower limit is set 1.1 times higher than the maximum load current () and for the relay to operate facing a fault, its upper limit is set equal to α times the minimum fault current that the relay observes in the backup mode ().
()

2.3.2. TDS

Another constraint is applied to TDS, which is essential to provide coordination between the relays. and are the TDSs of the ith relay for the operation of the relay in the main and backup modes, respectively. For each of these decision variables, upper limits TDSmax = 0.32 and lower limits TDSmin = 0.05 are considered as presented in equations (5) and (6).
()
()

2.3.3. IH

Point H is the breakpoint in the characteristic curve as shown in Figure 1(b). If the fault current of the relay is less than the current value of IH, the relay operates as a backup using characteristic curve type 1. If the fault current exceeds the IH value, the relay switches to characteristic curve type 2, and the relay operates in primary protection mode. Another constraint that must be observed is the upper and lower limits of point H as follows.
()
where is the maximum current of the ith relay in the backup mode and is the minimum current of that relay in the main mode.

2.3.4. Curves

In the proposed method, the operation time of the relays in the main or backup mode is obtained according to the IEC standard and based on the following equation.
()
where tij is the operation time of the ith relay at the jth fault location. Ifij is the current that ith relay observes for fault at the jth location. Ipi indicates the pickup current of the ithth relay. As shown in Table 2, A and B are the coefficients of the characteristic curve, which are selected based on the type of curve. In the main protection mode, the curve uses coefficients from the NI, VI, and EI curves. In backup mode, the curve selects coefficients from the NI and VI curves.
Table 2. Characteristic curve coefficients.
Curve type A B
Normal Inverse 0.14 0.02
Very Inverse 13.5 1
Extremely Inverse 80 2
As shown in equation (9), in the proposed protection scheme, to make the simulation environment more similar to reality, according to the relay catalog [25], when the ratio of the fault current to the relay Ip is more than 20, the relay operation time is no longer reduced. Therefore, in the simulations, the maximum value of the ratio of the fault current to Ip of a relay is considered equal to 20, as shown in equation (10).
()
()

Superscripts pm and bk indicate main and backup modes, respectively.

2.4. Optimization Algorithm

To minimize the objective function, various optimization algorithms such as GA particle swarm optimization (PSO) algorithm, shuffled frog leaping algorithm (SFLA), teaching learning optimization algorithm (TLBO), and other metaheuristic algorithms can be used. However, according to the results of previous studies, the GA has favorable behavior and convergence in objective functions with many decision variables [15]. Therefore, GA is used to find the optimal values of the decision variables in the proposed protection coordination scheme. In the genetic algorithm, the values of the decision variables are initially created randomly within the range of their variation. Then, by calculating the fitness function and minimizing the operation time of each relay, the optimal values of the decision variables are selected. Table 3 presents the settings considered for the genetic algorithm parameters in the proposed design.

Table 3. GA settings.
Parameter Value
Population size 200
Iterations 4000
Crossover rate 0.6
Mutation rate 0.4

In Figure 2, the chromosomes of the decision variables of the DOC relays are shown. In the studied network, 29 DOC relays are used. Therefore, in the GA, the first 29 genes of each chromosome (1–29) include the relays’ TDSs in the main mode. The following 29 genes (30–58) include the relays’ TDSs in the backup mode. The next 29 genes (59–87) include the relays Ip and the next 29 genes (88–116) include the point H current. The following 29 genes (117–145) include the main relay curve type, and the final 29 genes (146–174) include the backup relay curve type. The NI, VI, and EI curves are considered as numbers 1, 2, and 3, respectively. Therefore, the number of decision variables in the proposed algorithm for the specific study case is equal to 174.

Details are in the caption following the image
Chromosomes of GA.

2.5. Flowchart

In Figure 3, the flowchart of the proposed protection coordination scheme is presented. First, the test system is simulated in DIGSILENT software, and based on load flow studies, the load currents that pass through the relays are obtained. These studies are carried out in both grid-connected and islanded modes. Then, the obtained currents are fed into the MATLAB software, and the GA optimization is run to obtain the optimal values of the decision variables.

Details are in the caption following the image
Flowchart of the proposed method.

3. Description of the Test System

The proposed protection coordination scheme is tested on the modified IEEE 30-bus distribution system [26]. As shown in Figure 4, this network comprises 14 buses and 16 feeders, whose parameters are given in [26]. In addition, the network utilizes 29 directional overcurrent relays. The network nominal voltage is 33 kV, the frequency is 60 Hz, and the test system consists of three subtransmission substations with 132/33 kV and 50 MVA transformers. The studied network also includes 11 synchronous-based DGs in buses (2–10, 12, and 14). In the case of the islanded mode of operation, synchronous-based DGs can supply all the local loads. Synchronous-based DGs are connected to the network by 11 transformers of 6.6/33 kV [26].

Details are in the caption following the image
The distribution section of the IEEE 30-bus system.

4. Simulation Results and Analysis

In this section, the first subsection presents the operation time of the relays in both grid-connected and islanded modes, as well as the optimal settings of the protection relays, obtained using the method described in reference [24]. Then, in the second subsection, the operation time of the relays in both grid-connected and islanded modes, along with the optimal settings of the relays, are obtained using the proposed method. In both subsections, by applying a symmetrical fault in the middle of each line, the fault current of each relay is recorded. The CTI used in reference [24] and the proposed method are identical and equal to 0.2 s. In addition, at the end of the second subsection, it is demonstrated that the relay operation time achieved by the proposed method is reduced compared with the reference method. Then, in the third subsection, the operation times of the relays in grid-connected and islanded modes, as well as the optimal settings of the relays for all symmetrical and unsymmetrical faults, are obtained using the proposed method.

4.1. The Method of Optimizing Dual Characteristic in Reference [24] With Symmetrical Faults

In reference [24], using the dual characteristic, which consists of two protection curves (VI curve for the main relay and NI curve for the backup relay), has been proposed. In that reference, three decision variables have been considered for each DOCR, which include (, , and Ip). The optimum relay setting for this method is given in Table 4. Table 5 presents the operation time of the relays in the islanded mode, and Table 6 displays the operation time of the relays in the grid-connected mode.

Table 4. Optimum values of relay settings based on reference [24] with symmetrical faults.
Relay Ip (pu) TDS (main) TDS (backup) H setting
1 0.0714 0.05 0.1474 24.88
2 0.2341 0.05 0.0561 5.535
3 0.0459 0.05 0.1125 31.85
4 0.0295 0.05 0.0965 16.76
5 0.0435 0.05 0.0807 17.48
6 0.1557 0.05 0.0689 7.697
7 0.2607 0.05 0.0502 4.826
8 0.0314 0.05 0.0578 27.34
9 0.0976 0.05 0.1069 14.72
10 0.0628 0.05 0.1067 19.99
11 0.0263 0.05 0.0941 30.28
12 0.0799 0.05 0.0932 15.19
13 0.2095 0.05 0.0747 5.911
14 0.3422 0.05 0.0516 3.712
15 0.0742 0.05 0.0941 16.46
16 0.0891 0.05 0.0668 12.11
17 0.0964 0.05 0.1035 10.75
18 0.0281 0.05 0.1721 37.39
19 0.0774 0.05 0.0685 13.61
20 0.0595 0.05 0.0513 24.73
21 0.1061 0.05 0.0523 9.744
22 0.1002 0.05 0.0511 6.793
23 0.0227 0.05 0.1399 34.36
24 0.0293 0.05 0.1015 23.29
25 0.1062 0.05 0.0526 4.758
26 0.0531 0.05 0.0779 10.74
27 0.0161 0.05 0.1428 26.76
28 0.0263 0.05 0.1958 11.55
29 0.0101 0.05 0.1654 38.89
Table 5. Operating time of relays in the islanded mode based on reference [24] with symmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0356 0.3591 0.3402
  
F16 R8 R6 R16 R22
0.0357 0.4017 0.2814 0.2934
  
F17 R6 R12
0.2527 0.4529
R9 R16 R22
0.0474 0.2478 0.2479
  
F18 R10 R6 R22
0.0356 0.3792 0.2824
R16 R18
0.1895 0.3903
  
F19 R7 R9
0.2314 0.4353
R12 R14
0.2444 0.4446
  
F20 R17 R10
0.0632 0.2871
R18 R2
0.0356 0.3327
  
F21 R13 R7
0.1282 0.3719
R14 R1
0.2247 0.4267
  
F22 R2 R15 R20 R23
0.1396 0.3397 0.1918 0.3404
R19 R17
0.1856 0.3879
  
F23 R1 R19 R20 R23
0.0356 0.2426 0.2364 0.3172
R15 R13
0.2442 0.4446
  
F24 R3 R15 R19 R23
0.0355 0.2728 0.2355 0.3172
R20 R23 R4
0.1172 0.3172 0.3174
  
F25 R4 R15 R19
0.0355 0.2861 0.2504
R21 R3
0.0579 0.2584
R23 R11 R25
0.0356 0.2916 0.3761
  
F26 R11 R6 R16
0.0359 0.5569 0.3555
R22 R4 R21 R25
0.0803 0.4541 0.3262 0.4668
  
F27 R24 R4 R11 R21
0.0355 0.4153 0.2873 0.3618
R25 R29
0.1748 0.3751
  
F28 R26 R24
0.0623 0.2627
R29
0.0357
  
F29 R27 R24 R29
0.0356 0.2577 0.3751
  
F30 R28 R26
0.0356 0.2896
  • Note: The first row of Table 5 is bold to emphasize the titles.
Table 6. Operating time of relays in the grid-connected mode based on reference [24] with symmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0365 0.4665 0.4181
  
F16 R8 R6 R16 R22
0.0357 0.2372 0.2888 0.2848
  
F17 R6 R12
0.0978 0.6347
R9 R16 R22
0.0396 0.4682 0.4056
  
F18 R10 R6 R22
0.0356 0.2363 0.2579
R16 R18
0.0534 0.3903
  
F19 R7 R9
0.1192 0.4251
R12 R14
0.0401 0.2927
  
F20 R17 R10
0.0475 0.2485
R18 R2
0.0355 0.2359
  
F21 R13 R7
0.1008 0.3011
R14 R1
0.1196 0.3343
  
F22 R2 R15 R20 R23
0.0688 0.4151 0.2821 0.4061
R19 R17
0.0491 0.3307
  
F23 R1 R19 R20 R23
0.0356 0.2583 0.3378 0.3172
R15 R13
0.0374 0.3129
  
F24 R3 R15 R19 R23
0.0355 0.2668 0.2461 0.4073
R20 R23 R4
0.0363 0.4074 0.2704
  
F25 R4 R15 R19
0.0355 0.2993 0.2923
R21 R3
0.0355 0.2552
R23 R11 R25
0.0356 0.2361 0.2362
  
F26 R11 R6 R16
0.0359 1.2431 0.3763
R22 R4 R21 R25
0.0599 0.3042 0.2604 0.2892
  
F27 R24 R4 R11 R21
0.0355 0.3278 0.2714 0.3084
R25 R29
0.0431 0.5072
  
F28 R26 R24
0.0359 0.4224
R29
0.3751
  
F29 R27 R24 R29
0.0356 0.3653 0.5261
  
F30 R28 R26
0.0356 0.2365

The operation time of all relays in the main mode and in all operating modes is mostly 0.035 s, and this operation time with curve VI cannot be less than this value; this result means that at these points, the short-circuit current is more than 20 times the load current of the relays. In fault location (F22) and in the island operation mode that is marked with bold in Table 5, the operation time of the main relay R2 is equal to 0.1396 s, and the operation time of the backup relay R20 is equal to 0.1918 s, which indicates that CTI is less than 0.2 s. Operation of these relays has caused the loss of CTI. The optimum relay setting for this method is given in Table 5.

4.2. Proposed Dual Characteristic Optimization Method With Symmetrical Faults

In this subsection, the results obtained from the proposed protection coordination method, using the objective function in equation (1), are presented. In addition, a comparison is made between the operation times of the relays in all operating modes for the proposed method and the reference method [24]. In the proposed protection method for each DOCR, six decision variables are considered, which include (, , Ip, IH, and main protection curves and backup protection curves).

Table 7 shows the optimal settings obtained for the decision variables in the proposed protection method. Table 8 presents the operation time of the relays in the islanded mode, and Table 9 displays the operation time of the relays in the grid-connected mode.

Table 7. Optimum values of relay settings based on the proposed method with symmetrical faults.
Relay Ip (pu) TDS (main) TDS (backup) H setting Type 2 Type 1
1 0.0213 0.05 0.1031 84.83 EI NI
2 0.0356 0.05 0.1024 39.01 EI NI
3 0.0785 0.05 0.2319 21.51 EI VI
4 0.0238 0.05 0.2275 27.38 EI VI
5 0.0207 0.05 0.3125 73.51 EI NI
6 0.1487 0.05 0.0635 9.06 EI NI
7 0.2186 0.05 0.0536 5.74 EI VI
8 0.0312 0.05 0.2745 53.87 EI VI
9 0.0593 0.05 0.2158 25.21 EI VI
10 0.0923 0.05 0.1826 14.59 EI VI
11 0.0549 0.05 0.0609 18.67 EI NI
12 0.0482 0.05 0.1887 22.81 EI VI
13 0.2431 0.05 0.0609 5.42 EI NI
14 0.1236 0.05 0.1309 11.16 EI VI
15 0.0165 0.05 0.0937 81.47 EI NI
16 0.0428 0.05 0.0801 26.31 EI NI
17 0.0771 0.05 0.2107 14.61 EI VI
18 0.0905 0.05 0.1871 12.81 EI VI
19 0.0177 0.05 0.0953 57.26 EI NI
20 0.0511 0.05 0.0623 24.59 EI NI
21 0.0409 0.05 0.1465 32.75 EI VI
22 0.0225 0.05 0.0906 42.11 EI NI
23 0.0201 0.05 0.1507 42.37 EI NI
24 0.0277 0.05 0.0863 32.07 EI NI
25 0.0276 0.05 0.0901 18.75 EI NI
26 0.0298 0.05 0.2518 21.25 EI VI
27 0.0141 0.05 0.1371 59.62 EI VI
28 0.0102 0.05 0.0678 76.32 EI VI
29 0.0193 0.05 0.0743 16.06 EI VI
Table 8. Operating time of relays in the islanded mode based on the proposed method with symmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0107 0.2491 0.2575
  
F16 R8 R6 R16 R22
0.0101 0.3559 0.2308 0.2289
  
F17 R6 R12
0.2271 0.4346
R9 R16 R22
0.0105 0.2111 0.2113
  
F18 R10 R6 R22
0.0198 0.3366 0.2249
R16 R18
0.1814 0.3839
  
F19 R7 R9
0.1672 0.3672
R12 R14
0.1341 0.3397
  
F20 R17 R10
0.0191 0.3241
R18 R2
0.0264 0.2321
  
F21 R13 R7
0.1435 0.3543
R14 R1
0.0326 0.2337
  
F22 R2 R15 R20 R23
0.0101 0.2124 0.2147 0.3505
R19 R17
0.0162 0.4169
  
F23 R1 R19 R20 R23
0.0101 0.2162 0.2602 0.3418
R15 R13
0.2124 0.4161
  
F24 R3 R15 R19 R23
0.0102 0.2124 0.2162 0.3417
R20 R23 R4
0.1413 0.3417 0.3414
  
F25 R4 R15 R19
0.0108 0.2124 0.2162
R21 R3
0.0108 0.3042
R23 R11 R25
0.0101 0.2852 0.2657
  
F26 R11 R6 R16
0.0112 0.4865 0.2701
R22 R4 R21 R25
0.0101 0.7003 0.2885 0.2896
  
F27 R24 R4 R11 R21
0.0103 0.5948 0.2789 0.3269
R25 R29
0.0114 0.2123
  
F28 R26 R24
0.0104 0.2186
R29
0.0154
  
F29 R27 R24 R29
0.0105 0.2145 0.2311
  
F30 R28 R26
0.0101 0.3301
Table 9. Operating time of relays in the grid-connected mode based on the proposed method with symmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0107 0.4166 0.3797
  
F16 R8 R6 R16 R22
0.0101 0.2134 0.2351 0.2258
  
F17 R6 R12
0.0452 0.7105
R9 R16 R22
0.0105 0.3196 0.2616
  
F18 R10 R6 R22
0.0105 0.2114 0.2155
R16 R18
0.0101 0.2671
  
F19 R7 R9
0.0582 0.3512
R12 R14
0.0103 0.2108
  
F20 R17 R10
0.0112 0.2121
R18 R2
0.0142 0.2321
  
F21 R13 R7
0.0941 0.2957
R14 R1
0.0117 0.2337
  
F22 R2 R15 R20 R23
0.0101 0.2124 0.3049 0.4149
R19 R17
0.0102 0.2944
  
F23 R1 R19 R20 R23
0.0101 0.2162 0.3577 0.3417
R15 R13
0.0102 0.2808
  
F24 R3 R15 R19 R23
0.0102 0.2124 0.2162 0.4161
R20 R23 R4
0.0102 0.4161 0.2319
  
F25 R4 R15 R19
0.0108 0.2124 0.2162
R21 R3
0.0108 0.2116
R23 R11 R25
0.0101 0.2112 0.2124
  
F26 R11 R6 R16
0.0103 1.0224 0.2801
R22 R4 R21 R25
0.0101 0.3094 0.2114 0.2357
  
F27 R24 R4 R11 R21
0.0103 0.3669 0.2566 0.2684
R25 R29
0.0101 0.3799
  
F28 R26 R24
0.0104 0.3472
R29
0.1825
  
F29 R27 R24 R29
0.0105 0.3016 0.4035
  
F30 R28 R26
0.0101 0.2131

As can be seen, the CTI is maintained at all fault locations. In addition, due to the use of the curve EI, the operation time of most relays in the main mode has been reduced to 0.01 s in both islanded and grid-connected operating modes, compared with 0.035 s in Tables 5, 6.

The operation time of the relays in the backup mode has also been reduced. Some comparisons between the results of reference [24] and the proposed method are as follows.

As shown in Figure 5 for the fault at the F15 location in the grid-connected mode, relay R5 operates as the main relay, while relays R9 and R12 serve as backup relays. If relay R5 fails to operate, the backup relays operate after 0.4166 s and 0.3797 s, respectively, to isolate the fault. According to the method described in reference [24], the backup relays operate with response times of 0.4665 s and 0.4181 s, respectively, which show that the proposed method has improved the relays’ operating times.

Details are in the caption following the image
Comparison of performance of relays in F15 location with symmetrical faults.

For faults at the F15 location and in the islanded mode, relay R5 operates as the main relay, while relays R9 and R12 function as backup relays. If relay R5 fails to operate, the backup relays operate after 0.2491 s and 0.2575 s, respectively, to isolate the fault. According to the method described in reference [24], the backup relays operate with the times of 0.3591 s and 0.3402 s, respectively. The proposed method demonstrates improvement over the previous study.

As shown in Figure 6 for the fault in the F22 location in the grid-connected mode, relays R2 and R19 operate as the main relays, while relays R15, R20, R23, and R17 operate as backup relays. If relay R2 fails to operate, the backup relays operate after 0.2124 s, 0.3049 s, and 0.4149 s, respectively, to isolate the fault. If relay R19 fails to operate, the backup relay operates after 0.2944 s. While using the method presented in reference [24], the backup relays operate with the times of 0.4151 s, 0.2821 s, 0.4061 s, and 0.3307 s, respectively.

Details are in the caption following the image
Comparison of performance of relays in F22 location with symmetrical faults.

For the fault in the F22 location and in the islanded mode, relays R2 and R19 operate as the main relays, while relays R15, R20, R23, and R17 operate as backup relays. If relay R2 fails to operate, the backup relays operate after 0.2124 s, 0.2147 s, and 0.3505 s, respectively, to isolate the fault. If relay R19 fails to operate, the backup relay operates after 0.4169 s. While using the method presented in reference [24], the backup relays operate with times of 0.3397 s, 0.1918 s, 0.3404 s, and 0.3879 s, respectively.

In reference [24], the CTI between the main and backup relays was considered to be 0.2 s. As you can see, here, the time interval between relay R2 and R20 has disappeared, which is why the R20 relay diagram is shown in red. But the proposed method maintains the CTI between the main and backup relays.

Another notable point in Figure 6 is the slight increase in the operation time of some backup relays in the proposed design compared with the reference. This increase in time is negligible compared with the decrease in time in other main and backup relays and also helps to maintain CTI.

In Table 10, the operation time of the relays in the proposed coordination method is compared with that in reference [24]. As can be seen, the proposed method reduces the operation time of the relays by 17% in all operating modes.

Table 10. Comparison of the reduction of the operation time of the relays in the proposed protection scheme compared with reference [24] with symmetrical faults.
Operating mode Benchmark method with symmetrical faults [24] (s) Proposed method with symmetrical faults (s) Percentage of improvement (%)
Grid-connected operation mode 18.7 15.2 19
Islanded operation mode 19.1 16.3 15
Summation (both modes) 37.8 31.5 17

Simulations have been carried out using a Core i7-7500U/8GB RAM laptop, and it takes approximately 20 min. In Figure 7, the convergence of the genetic algorithm and its comparison with reference [24] are presented.

Details are in the caption following the image
GA convergence and comparison with reference [24] with symmetrical faults.

4.3. Proposed Dual Characteristic Optimization Method With Symmetrical and Unsymmetrical Faults

The settings of directional overcurrent relays should cover all possible fault scenarios, including the worst-case scenario and the highest current, such as a three-phase fault or faults with lower current, such as single-phase to ground, two-phase, and two-phase to ground faults. Therefore, in this subsection, using the objective function of equation (3), settings are presented that include all the mentioned modes, which were not considered in previous studies. Table 11 presents the optimal settings obtained for the decision variables in the proposed protection method for both symmetrical and unsymmetrical faults. Table 12 presents the operation time of the relays in the islanded mode, and Table 13 displays the operation time of the relays in the grid-connected mode.

Table 11. Optimal values of relay settings based on the proposed method with symmetrical and unsymmetrical faults.
Relay Ip (pu) TDS (main) TDS (backup) H setting Type 2 Type 1
1 0.3596 0.05 0.0613 5.02 EI NI
2 0.1665 0.05 0.0921 8.33 EI VI
3 0.3201 0.11 0.0511 5.27 VI NI
4 0.0418 0.05 0.1109 15.56 EI VI
5 0.0207 0.05 0.2771 73.51 EI VI
6 0.0522 0.05 0.0935 24.98 EI NI
7 0.0938 0.19 0.0992 12.99 VI VI
8 0.0312 0.05 0.1576 53.88 EI NI
9 0.1223 0.05 0.1741 12.21 EI VI
10 0.0634 0.05 0.0893 21.23 EI NI
11 0.0818 0.05 0.0986 12.54 EI NI
12 0.1042 0.05 0.0591 10.38 EI NI
13 0.0192 0.05 0.0932 68.31 EI NI
14 0.1249 0.05 0.1216 11.04 EI VI
15 0.0165 0.05 0.1912 72.04 EI NI
16 0.0275 0.05 0.0966 38.39 EI NI
17 0.0674 0.05 0.1752 16.72 EI VI
18 0.0598 0.05 0.2314 19.36 EI VI
19 0.0699 0.05 0.1364 15.09 EI NI
20 0.0635 0.05 0.1251 19.51 EI NI
21 0.0799 0.05 0.1024 16.79 EI VI
22 0.0338 0.05 0.0862 28.01 EI NI
23 0.1281 0.08 0.1128 6.62 NI NI
24 0.0304 0.05 0.0941 29.23 EI NI
25 0.0877 0.05 0.1071 5.89 EI NI
26 0.0856 0.05 0.0662 7.39 EI VI
27 0.0141 0.05 0.3815 59.63 EI NI
28 0.0179 0.05 0.3286 76.32 EI VI
29 0.0181 0.05 0.0938 38.76 EI NI
Table 12. Operating time of relays in the islanded mode based on the proposed method with symmetrical and unsymmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0101 0.4558 0.2486
  
F16 R8 R6 R16 R22
0.0101 0.2707 0.2317 0.2629
  
F17 R6 R12
0.0101 0.2102
R9 R16 R22
0.0179 0.2191 0.2331
  
F18 R10 R6 R22
0.0101 0.2612 0.2533
R16 R18
0.0101 0.2799
  
F19 R7 R9
0.1755 0.3768
R12 R14
0.0226 0.3118
  
F20 R17 R10
0.0101 0.2389
R18 R2
0.0102 0.3466
  
F21 R13 R7
0.0101 0.2108
R14 R1
0.1639 0.3659
  
F22 R2 R15 R20 R23
0.0411 0.4335 0.4405 0.5749
R19 R17
0.0126 0.2779
  
F23 R1 R19 R20 R23
0.1533 0.4463 0.3551 0.5226
R15 R13
0.0107 0.2114
  
F24 R3 R15 R19 R23
0.2331 0.4335 0.4333 0.4338
R20 R23 R4
0.0102 0.4338 0.3201
  
F25 R4 R15 R19
0.0104 0.4335 0.4668
R21 R3
0.0101 0.2978
R23 R11 R25
0.2915 0.6352 0.6498
  
F26 R11 R6 R16
0.0189 0.3194 0.2655
R22 R4 R21 R25
0.2638 0.7619 0.4681 0.8608
  
F27 R24 R4 R11 R21
0.0101 0.6704 0.6671 0.5691
R25 R29
0.0548 0.3594
  
F28 R26 R24
0.0551 0.2562
R29
0.0101
  
F29 R27 R24 R29
0.0102 0.2521 0.2128
  
F30 R28 R26
0.0101 0.3343
Table 13. Operating time of relays in the grid-connected mode based on the proposed method with symmetrical and unsymmetrical faults.
Fault location Main relay operation time Backup relay operation time Backup relay operation time Backup relay operation time
F15 R5 R9 R12
0.0101 0.6482 0.2847
  
F16 R8 R6 R16 R22
0.0101 0.2135 0.2341 0.2614
  
F17 R6 R12
0.0101 0.2177
R9 R16 R22
0.0111 0.2191 0.2111
  
F18 R10 R6 R22
0.0101 0.2121 0.2437
R16 R18
0.0101 0.2106
  
F19 R7 R9
0.1355 0.5171
R12 R14
0.0123 0.2125
  
F20 R17 R10
0.0101 0.2107
R18 R2
0.0102 0.2111
  
F21 R13 R7
0.0101 0.2104
R14 R1
0.0102 0.2125
  
F22 R2 R15 R20 R23
0.0157 0.4335 0.5434 0.6129
R19 R17
0.0101 0.2108
  
F23 R1 R19 R20 R23
0.0304 0.4523 0.3499 0.5179
R15 R13
0.0106 0.2114
  
F24 R3 R15 R19 R23
0.0933 0.4335 0.4328 0.2947
R20 R23 R4
0.0101 0.2947 0.2111
  
F25 R4 R15 R19
0.0101 0.4335 0.5108
R21 R3
0.0101 0.2103
R23 R11 R25
0.2538 0.4541 0.4572
  
F26 R11 R6 R16
0.0117 0.2358 0.2718
R22 R4 R21 R25
0.0103 0.4465 0.6352 0.4973
  
F27 R24 R4 R11 R21
0.0101 0.4465 0.6352 0.4973
R25 R29
0.0101 0.2408
  
F28 R26 R24
0.0163 0.3918
R29
0.0101
  
F29 R27 R24 R29
0.0102 0.3394 0.2466
  
F30 R28 R26
0.0101 0.2103

To test the obtained optimal settings using the objective function of equation (3) in the presence of high resistance faults, a new case study is considered. In this case study, the fault currents for single-phase to ground and two-phase short circuit faults are considered to be half and one-quarter of the three-phase fault current, respectively. Table 14 presents a comparison of the total operating time between the proposed method and the benchmark method [24] for symmetrical and unsymmetrical faults, both without and with resistance. It is clear from Table 14 that the proposed method outperforms the other methods at all faults.

Table 14. Operation time of the relays in case of symmetrical faults, symmetrical and unsymmetrical faults without resistance, and symmetrical and unsymmetrical faults with resistance for the proposed method.
Faults type Operating mode Benchmark method [24] Proposed method Percentage of improvement (%)
Symmetrical faults Grid-connected operation mode 18.7 15.2 19
Islanded operation mode 19.1 16.3 15
Summation (both modes) 37.8 31.5 17
  
Symmetrical and unsymmetrical faults without resistance Grid-connected operation mode 20.9 17.2 18
Islanded operation mode 24.1 20.2 16
Summation (both modes) 45 37.4 17
  
Symmetrical and unsymmetrical faults with resistance Grid-connected operation mode 39.5 32.5 18
Islanded operation mode 49.7 40.4 19
Summation (both modes) 89.2 72.9 18

5. Conclusion

In general, studies on the coordination of protection for microgrids in the presence of DGs can be divided into two categories: methods based on communication systems and methods that do not require a communication system. In this paper, the aim was to present a protection scheme based on overcurrent protection with dual characteristics for AC microgrids without the need for a communication platform. By reducing the operating time of the relays in both grid-connected and islanded operating modes, CTI was also maintained between the main and backup relay operations. Therefore, three types of curves were considered for the function of the relay as the main relay, which included NI, VI, and EI curves. Two types of curves were considered for the function of the relay as a backup relay, namely, NI and VI curves. In the proposed protection method for each DOCR, six decision variables were considered, which include , , Ip, IH, and main protection curves and backup protection curves. According to the results obtained, the following goals are also achieved:
  • Presenting a new objective function to consider both symmetrical and unsymmetrical faults in the optimization procedure.

  • Reducing the operation time of the relays and thus the protection system by using dual characteristics in symmetrical and unsymmetrical faults by 17%.

  • Maintaining the minimum CTI between the main and backup relays in all operating modes.

  • Increasing reliability against cyber-attacks and possible failure of communication systems by using the communication-free scheme.

Conflicts of Interest

The authors declare no conflicts of interest.

Funding

No funding was received for this manuscript.

Data Availability Statement

Data sharing not applicable to this article as no datasets were generated or analyzed during the current study.

    The full text of this article hosted at iucr.org is unavailable due to technical difficulties.